| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Multiple buffer overflows in ActUWzd.dll 1.0.0.1 in Mitsubishi MX Component 3, as distributed in Citect CitectFacilities 7.10 and CitectScada 7.10r1, allow remote attackers to execute arbitrary code via a long string, as demonstrated by a long WzTitle property value to a certain ActiveX control. |
| The modbus_125_handler function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) allows remote attackers to install arbitrary firmware updates via a MODBUS 125 function code to TCP port 502. |
| The ComputePassword function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) generates the password for the fwupgrade account by performing a calculation on the MAC address, which makes it easier for remote attackers to obtain access via a (1) ARP request message or (2) Neighbor Solicitation message. |
| The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port. |
| The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions. |
| Cross-site scripting (XSS) vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| The Schneider Electric M340 BMXNOE01xx and BMXP3420xx PLC modules allow remote authenticated users to cause a denial of service (module crash) via crafted FTP traffic, as demonstrated by the FileZilla FTP client. |
| Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to execute arbitrary code or cause a denial of service via unspecified vectors. |
| Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors. |
| Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric Kerweb before 3.0.1 and Kerwin before 6.0.1 allow remote attackers to inject arbitrary web script or HTML via (1) the evtvariablename parameter in an evts.xml action to kw.dll, (2) unspecified search fields, or (3) unspecified content-display fields. |
| The Schneider Electric Magelis XBT HMI controller has a default password for authentication of configuration uploads, which makes it easier for remote attackers to bypass intended access restrictions via crafted configuration data. |
| Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to cause a denial of service via unspecified vectors. |
| Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| Schneider Electric Trio J-Series License Free Ethernet Radio with firmware 3.6.0 through 3.6.3 uses the same AES encryption key across different customers' installations, which makes it easier for remote attackers to defeat cryptographic protection mechanisms by leveraging knowledge of this key from another installation. |
| Cross-site scripting (XSS) vulnerability in Schneider Electric Modicon Quantum PLC allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| Heap-based buffer overflow in RFManagerService.exe in Schneider Electric Accutech Manager 2.00.1 and earlier allows remote attackers to execute arbitrary code via a crafted HTTP request. |
|
A CWE-502: Deserialization of Untrusted Data vulnerability exists in the Dashboard module that
could cause an interpretation of malicious payload data, potentially leading to remote code
execution when an attacker gets the user to open a malicious file.
|
|
A CWE-427 - Uncontrolled Search Path Element vulnerability exists that could allow an attacker
with a local privileged account to place a specially crafted file on the target machine, which may
give the attacker the ability to execute arbitrary code during the installation process initiated by a
valid user. Affected Products: Easergy Builder Installer (1.7.23 and prior) |
|
A CWE-863: Incorrect Authorization vulnerability exists that could allow access to device
credentials on specific DCE endpoints not being properly secured when a hacker is using a low
privileged user.
Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)
|
|
A CWE-862: Missing Authorization vulnerability exists that could allow viewing of unauthorized
content, changes or deleting of content, or performing unauthorized functions when tampering
the Device File Transfer settings on DCE endpoints.
Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)
|