CVE-2019-6962 1 Rdkcentral 1 Rdkb Ccsppandm 2024-11-21 N/A
A shell injection issue in cosa_wifi_apis.c in the RDK RDKB-20181217-1 CcspWifiAgent module allows attackers with login credentials to execute arbitrary shell commands under the CcspWifiSsp process (running as root) if the platform was compiled with the ENABLE_FEATURE_MESHWIFI macro. The attack is conducted by changing the Wi-Fi network password to include crafted escape characters. This is related to the WebUI module.
CVE-2019-6957 1 Bosch 18 Access Easy Controller, Access Easy Controller Firmware, Access Professional Edition and 15 more 2024-11-21 9.8 Critical
A recently discovered security vulnerability affects all Bosch Video Management System (BVMS) versions 9.0 and below, DIVAR IP 2000, 3000, 5000 and 7000, Video Recording Manager (VRM), Video Streaming Gateway (VSG), Configuration Manager, Building Integration System (BIS) with Video Engine, Access Professional Edition (APE), Access Easy Controller (AEC), Bosch Video Client (BVC) and Video SDK (VSDK). The vulnerability potentially allows the unauthorized execution of code in the system via the network interface.
CVE-2019-6859 1 Schneider-electric 20 140 Cpu6x, 140 Cpu6x Firmware, 140 Noc 77101 and 17 more 2024-11-21 7.5 High
A CWE-798: Use of Hardcoded Credentials vulnerability exists in Modicon Controllers (All versions of the following CPUs and Communication Module product references listed in the Security Notifications), which could cause the disclosure of FTP hardcoded credentials when using the Web server of the controller on an unsecure network.
CVE-2019-6853 1 Schneider-electric 22 Andover Continuum 5720, Andover Continuum 5720 Firmware, Andover Continuum 5740 and 19 more 2024-11-21 6.1 Medium
A CWE-79: Failure to Preserve Web Page Structure vulnerability exists in Andover Continuum (models 9680, 5740 and 5720, bCX4040, bCX9640, 9900, 9940, 9924 and 9702) , which could enable a successful Cross-site Scripting (XSS attack) when using the products web server.
CVE-2019-6848 1 Schneider-electric 6 Modicon Bmenoc 0311, Modicon Bmenoc 0311 Firmware, Modicon Bmenoc 0321 and 3 more 2024-11-21 8.6 High
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 CPU (BMEx58*) and Modicon M580 communication module (BMENOC0311, BMENOC0321) (see notification for version info), which could cause a Denial of Service attack on the PLC when sending specific data on the REST API of the controller/communication module.
CVE-2019-6847 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.9 Medium
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the FTP service when upgrading the firmware with a version incompatible with the application in the controller using FTP protocol.
CVE-2019-6844 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.9 Medium
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service atack on the PLC when upgrading the controller with a firmware package containing an invalid web server image using FTP protocol.
CVE-2019-6843 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.9 Medium
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 with firmware (version prior to V3.10), Modicon M340 (all firmware versions), and Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the controller with an empty firmware package using FTP protocol.
CVE-2019-6842 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.9 Medium
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the firmware with a missing web server image inside the package using FTP protocol.
CVE-2019-6841 1 Schneider-electric 8 Modicon 140cra, Modicon 140cra Firmware, Modicon Bmxcra and 5 more 2024-11-21 4.9 Medium
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 with firmware (version prior to V3.10), Modicon M340 (all firmware versions), and Modicon BMxCRA and 140CRA modules (all firmware versions), which could cause a Denial of Service attack on the PLC when upgrading the firmware with no firmware image inside the package using FTP protocol.
CVE-2019-6835 1 Schneider-electric 8 Meg6260-0410, Meg6260-0410 Firmware, Meg6260-0415 and 5 more 2024-11-21 5.4 Medium
A Cross-Site Scripting (XSS) CWE-79 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could allow an attacker to inject client-side script when a user visits a web page.
CVE-2019-6831 1 Schneider-electric 2 Bmxnor0200h, Bmxnor0200h Firmware 2024-11-21 8.6 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause disconnection of active connections when an unusually high number of IEC 60870- 5-104 packets are received by the module on port 2404/TCP.
CVE-2019-6830 1 Schneider-electric 2 Modicon M580, Modicon M580 Firmware 2024-11-21 5.9 Medium
A CWE-248: Uncaught Exception vulnerability exists IN Modicon M580 all versions prior to V2.80, which could cause a possible denial of service when sending an appropriately timed HTTP request to the controller.
CVE-2019-6828 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 7.5 High
A CWE-248: Uncaught Exception vulnerability exists Modicon M580 (firmware version prior to V2.90), Modicon M340 (firmware version prior to V3.10), Modicon Premium (all versions), and Modicon Quantum (all versions), which could cause a possible denial of service when reading specific coils and registers in the controller over Modbus.
CVE-2019-6827 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-787: Out-of-bounds Write vulnerability exists in Interactive Graphical SCADA System (IGSS), Version 14 and prior, which could cause a software crash when data in the mdb database is manipulated.
CVE-2019-6813 1 Schneider-electric 4 Bmxnor0200h, Bmxnor0200h Firmware, Modicon M340 and 1 more 2024-11-21 7.5 High
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions) and Modicon M340 controller (all firmware versions), which could cause denial of service when truncated SNMP packets on port 161/UDP are received by the device.
CVE-2019-6812 1 Schneider-electric 2 Bmx-nor-0200h, Bmx-nor-0200h Firmware 2024-11-21 7.2 High
A CWE-798 use of hardcoded credentials vulnerability exists in BMX-NOR-0200H with firmware versions prior to V1.7 IR 19 which could cause a confidentiality issue when using FTP protocol.
CVE-2019-6811 1 Schneider-electric 4 Modicon Quantum 140noe77101, Modicon Quantum 140noe77101 Firmware, Modicon Quantum 140noe77111 and 1 more 2024-11-21 7.5 High
An Improper Check for Unusual or Exceptional Conditions (CWE-754) vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a power cycle to recover.
CVE-2019-6809 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 7.5 High
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware versions prior to V2.90), Modicon M340 (firmware versions prior to V3.10), Modicon Premium (all versions), Modicon Quantum (all versions), which could cause a possible denial of service when reading invalid data from the controller.
CVE-2019-6807 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2024-11-21 7.5 High
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a possible denial of service when writing sensitive application variables to the controller over Modbus.